RED ORCHIDEA Betriebsanleitung Seite 38

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 48
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 37
red
PELLET STOVES Chapter 4
INSTALLATION AND USE MANUAL
page 38
Operation Technical service - Rights reserved - Reproduction prohibited
4.15. LED 1 SIGNALS DURING OPERATION
LED 1 Off: stove awaiting ignition
LED 1 Flashing green: ignition
LED 1 Fixed green: stove fully ignited
LED 1 Flashing orange: switching off
LED 1 Flashing red: alarm in progress
LED 1 Fixed red: stove switched off after alarm
In the event of shutdown following a mains cut-off led 1 keeps flashing orange even after cooling.
4.16. ALARM SIGNALLING
In the case in which there is an operational anomaly, the stove emits a
warning tone and informs the user of the type of fault that has
occurred by means of the control panel.
The 5 leds over keyE (0/-1/-2/+1/+2) also light up to signal alarms. In
the event of alarm, Led 1 will flash red, there will be warning tone and
the type of alarm is identified by one of the five corresponding Leds.
The following table describes the possible alarms signalled by the stove
and some useful suggestions to solve the problem.
WARNING!
The alarm is signalled by LED1 in red plus the relative
LED (-2/-1/0/+1/+2) in orange.
LED
SIGNALLING
TYPE OF PROBLEM SOLUTION
Led 2.
Fire fails to ignite
Check the level of pellets in the hopper.
Check that the grate is properly inserted in its housin
g
and
does not have any obvious unburnt incrustations;
Led 1.
Fire goes out abnormally
Check the level of pellets in the hopper.
Check that the
g
rate is properly inserted in its housin
g
and
does not have any obvious unburnt incrustations;
Led 0.
Pellet hopper temperature exceeds foreseen
safety limit.
Structure has overheated due to reduced hea
t
dissipation.
Wait for the end of the coolin
g
phase, cancel the alarm
and relight the stove placing the fuel load to minimum on
led -2 (section 4.10) and increasin
g
the room fan speed
(knob A). If the alarm persists, contact technical support.
Led +1
Anomalous operation of smoke fan.
Check that the
g
rate does not have visible unburn
t
incrustations. If the alarm persists, contact technical
support.
Led +2
Smoke temperature too hi
g
h or smoke probe
faulty.
Wait for the end of the coolin
g
phase, cancel the alarm
and reli
g
ht the stove placin
g
the fuel load to minimum on
led -2 (section 4.10) and increasin
g
the room fan speed
(knob A). If the alarm persists, contact technical support.
Seitenansicht 37
1 2 ... 33 34 35 36 37 38 39 40 41 42 43 ... 47 48

Kommentare zu diesen Handbüchern

Keine Kommentare